CONNECTING AN EXTERNAL SET POINT
(4-20mA EMS-CONTROL)
The Harmony can take a 4-20mA signal from an Energy Manage-
ment System (EMS) or other signal source to change the set point
remotely (see pg. 28 for additional details).
The signal must be a two-wire 4-20mA.
A system sensor must be installed as described in the previous
section.
The External Set Point must be set up correctly (see pg. 12). These
settings will allow the Harmony to read and monitor the system
temperature and also monitor the 4-20mA input to remotely adjust
the Harmony set point to the desired value.
The Harmony can source the current for the 4-20mA input. It
provides an excitation voltage of 24VDC. If using the Harmony to
source the power, attach the (+) side of the 4-20mA input to the
Harmony EMS terminal marked +. Attach the (-) side of the 4-20mA
signal to the EMS terminal marked SIGNAL.
If the EMS or other signal sources the current (provides the
excitation voltage), attach the (+) side of the 4-20mA input to the
Harmony EMS terminal marked SIGNAL. Attach the (-) side of the
4-20mA input to the EMS terminal marked SHIELD.
WIRING THE SHUTDOWN
This feature can be used whenever it is desirable to turn off the
Harmony from a remote location or another controller.
A typical use for this feature would be to turn off all boiler stages
when an EMS panel no longer requires heat in the system.
When the Shutdown feature is enabled by closing a dry contact, all
active stages will immediately modulate down to low. They will
remain in low for 45 seconds and then turn off.
If the System Output relay was active, it will remain active until the
System Delay is over, then it will also turn off.
The Shutdown signal must be a dry contact only. No voltage can
be placed across the SHUTDOWN terminals.
Bring the two wires from the dry contact to the terminals marked
SHUTDOWN- A3, A4.
WIRING THE SYSTEM PROVE
EMS INPUT
+
SIGNAL
SHIELD
Harmony Sources Curren
t
24VDC Excitation Voltage
(+)
(-)
EMS
Input
EMS Sourcing Current
EMS INPUT
+
SIGNAL
SHIELD
(+)
(-)
EMS
Input
INSTINST
INSTINST
INST
ALLAALLA
ALLAALLA
ALLA
TIONTION
TIONTION
TION
INPUT WIRINGINPUT WIRING
INPUT WIRINGINPUT WIRING
INPUT WIRING
Dry Contact
Shutdown
Signal
TEMP
SHUTDOWN
NETWORK
SYSTEM
PROVE
T
+
S
INPUTS
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10